hp to Amps Calculator

Estimate the full-load current of a motor from its horsepower or kilowatt rating, supply voltage, efficiency and power factor.

🐎 hp to Amps Calculator
Motor shaft power
hp definition
Motor efficiency (illustrative 90 %)
%
50100
Supply voltage (V)
V
Power factor (illustrative 0.85)
Line-to-line voltage (V)
V
Power factor (illustrative 0.85)
DC supply voltage (V)
V
Full-load current
—
Shaft output
—
Electrical input
—
Apparent power
—
Losses as heat
—
Power factor used
—

Full-load line current
—
Shaft output
—
Electrical input
—
Apparent power
—
Losses as heat
—
Power factor used
—

Full-load current
—
Shaft output
—
Electrical input
—
Losses as heat
—
Efficiency used
—
Voltage used
—

The motor nameplate full-load amps is the authoritative figure for wiring and protection. This result is a formula estimate from your assumptions.

🐎 What is an hp to Amps Conversion?

An hp to amps conversion estimates the electric current a motor draws when it delivers a given mechanical power at its shaft. Horsepower is a unit of power for the mechanical output. Amps are the electrical current drawn from the supply. To connect them you need the supply voltage, the efficiency of the motor, and for AC the power factor and the number of phases. The mechanical power is first converted to watts (1 hp is 746 W in the electrical convention), divided by the efficiency to find the electrical input power, and then divided by the voltage, power factor and, for three-phase, the square root of 3.

The calculation is used when selecting a motor for a supply, checking that a generator or inverter is large enough, estimating the load on a circuit, or comparing different voltages. It also helps to understand why a 5 hp motor is a modest load on a 400 V three-phase supply but a heavy one on a 120 V single-phase circuit. The comparison between modes shows how the same shaft power produces very different currents: for example, a 5 hp motor draws about 21 A on a 230 V single-phase supply and about 7 A per line on 400 V three-phase, assuming 90 percent efficiency and a power factor of 0.85.

This page does not reproduce any look-up table of standard motor currents. It calculates from the formula using your own efficiency and power factor. Those two inputs default to 90 percent and 0.85 only as illustrative starting points. Real motors vary: a small single-phase motor can have an efficiency in the 60 to 80 percent range, and the power factor falls sharply when a motor runs lightly loaded. The nameplate on the motor lists the full-load amps for that exact machine, and that value is the one to use for choosing wire, overload protection and breakers, together with the rules in your local electrical code.

The calculator can also take kilowatts instead of horsepower, lets you choose between the 746 W electrical horsepower, the 745.7 W mechanical horsepower and the 735.5 W metric horsepower, and reports the electrical input, the apparent power and the heat losses. For the general watts to amps relationship see the watts to amps calculator, and for wire sizing use the wire gauge calculator.

📐 Formula

I  =  ( hp × 746 ) / ( V × η × PF )    (single-phase)
I = full-load current (A); in three-phase the line current
hp × 746 = shaft output power in watts; with kW input use kW × 1000 instead
η = motor efficiency as a fraction (90 percent is 0.90); input power = output power / η
PF = power factor (AC only); omit for DC
Three-phase: I = ( hp × 746 ) / ( √3 × VLL × η × PF ) with the line-to-line voltage
DC: I = ( hp × 746 ) / ( V × η )
Apparent power: S = V I for single-phase and √3 VLL I for three-phase
Example: 5 hp, 230 V, η = 0.90, PF = 0.85 gives 3730 / ( 230 × 0.90 × 0.85 ) = 21.2 A

📖 How to Use This Calculator

Steps

1
Choose the supply type. Pick single-phase AC, three-phase AC or DC to match the motor supply.
2
Enter the motor and supply data. Type the motor power in hp or kW, the supply voltage, your efficiency estimate and, for AC, the power factor. Change the hp definition only if you need 745.7 W or the metric figure.
3
Read the current and check the nameplate. The main box gives the full-load current, the other boxes give the input power, apparent power and losses, and the chart shows the sensitivity. Compare with the motor nameplate, which is authoritative.

💡 Example Calculations

Example 1 — 5 hp Motor on 230 V Single-phase

5 hp (746 W), 230 V, efficiency 90 percent, PF 0.85 (illustrative)

1
Shaft output = 5 × 746 = 3730 W
2
Electrical input = 3730 / 0.90 = 4144.4 W, so the losses are 414.4 W
3
I = 4144.4 / ( 230 × 0.85 ) = 21.199 A, and the apparent power is 230 × 21.199 = 4.876 kVA
Full-load current = 21.199 A
Try this example →

Example 2 — 1 hp Motor with a Poor Efficiency and Power Factor

1 hp, 230 V single-phase, efficiency 80 percent, PF 0.8 (illustrative)

1
Shaft output = 746 W and input = 746 / 0.80 = 932.5 W
2
I = 932.5 / ( 230 × 0.8 ) = 5.068 A
3
Compared with a 90 percent efficient motor at PF 0.9, which would draw 746 / ( 0.9 × 230 × 0.9 ) = 4.004 A, the weaker motor draws 27 percent more
Full-load current = 5.0679 A
Try this example →

Example 3 — 10 hp Three-phase Motor at 400 V

10 hp (746 W), 400 V line-to-line, efficiency 90 percent, PF 0.85 (illustrative)

1
Shaft output = 7460 W and input = 7460 / 0.90 = 8288.9 W
2
√3 × 400 × 0.85 = 588.9, so I = 8288.9 / 588.9 = 14.075 A
3
Apparent power S = √3 × 400 × 14.075 = 9.752 kVA
Full-load line current = 14.075 A
Try this example →

Example 4 — 15 kW Motor Entered in Kilowatts

15 kW shaft power, 400 V three-phase, efficiency 92 percent, PF 0.86 (illustrative)

1
Shaft output = 15,000 W and input = 15,000 / 0.92 = 16,304 W
2
√3 × 400 × 0.86 = 595.8, so I = 16,304 / 595.8 = 27.364 A
3
The 15 kW rating is 20.1 mechanical hp, so the result is consistent with a 20 hp class motor
Full-load line current = 27.364 A
Try this example →

Example 5 — 2 hp DC Motor on 120 V

2 hp (746 W), 120 V DC, efficiency 85 percent (illustrative)

1
Shaft output = 1492 W and input = 1492 / 0.85 = 1755.3 W
2
I = 1755.3 / 120 = 14.627 A
3
There is no power factor term for DC. At 240 V the current would halve to 7.314 A.
Full-load current = 14.627 A
Try this example →

❓ Frequently Asked Questions

How do you convert hp to amps?+
Convert hp to watts (1 hp = 746 W), divide by the efficiency to get the electrical input power, then divide by the supply voltage and, for AC, the power factor. For single-phase, I = hp x 746 / (V x efficiency x PF).
What is the formula for hp to amps for a three-phase motor?+
I = hp x 746 / (sqrt(3) x V x efficiency x PF), with V the line-to-line voltage. A 10 hp motor at 400 V, 90 percent efficiency and PF 0.85 draws 7460 / (1.732 x 400 x 0.9 x 0.85) = 14.08 A.
How many amps is a 5 hp motor?+
It depends on the voltage, phases, efficiency and power factor. At 230 V single-phase with 90 percent efficiency and PF 0.85 the calculation gives 21.2 A. Use the nameplate for the actual value.
Is 1 hp equal to 746 watts?+
The electrical horsepower used for motors is defined as exactly 746 W. The mechanical horsepower is about 745.7 W and the metric horsepower about 735.5 W. The difference is under 0.1 percent between the first two, so the calculator lets you pick.
Why do I need efficiency and power factor?+
Horsepower is the mechanical output at the shaft, and the motor wastes some energy as heat. The input must be larger than the output by 1 / efficiency. For AC, the power factor tells how much of the supply current does useful work.
Why is the nameplate current different from the calculated current?+
The nameplate figure is measured or specified for that particular motor at full load, using its real efficiency and power factor. A calculation with generic assumptions can differ by several percent, so the nameplate is the authoritative value.
Does this calculator size the breaker or the wire?+
No. Breaker, fuse, cable and overload sizing follow local electrical codes and use specified tables and multipliers, not just the computed current. This tool gives an estimate of the full-load current to check a design against.
How do I convert kW to amps for a motor?+
Select kW as the unit and enter the shaft power. The calculator uses the kW value directly as the output power, divides by efficiency for input power, and then applies the current formula for your supply.
What is the difference between hp to amps for single-phase and three-phase?+
For the same power and voltage, a three-phase motor draws a lower line current because the formula has the square root of 3 in the denominator. The same 5 hp load is 21.2 A single-phase at 230 V but only 7.0 A per line on 400 V three-phase with the same efficiency and PF.
Does the current rise when the voltage drops?+
Yes. For constant output power the current rises as the voltage falls, and a motor on a low supply can overheat. This is why voltage drop in long cable runs matters for motors.

How do you convert hp to amps?

Convert hp to watts (1 hp = 746 W), divide by the efficiency to get the electrical input power, then divide by the supply voltage and, for AC, the power factor. For single-phase, I = hp x 746 / (V x efficiency x PF).

What is the formula for hp to amps for a three-phase motor?

I = hp x 746 / (sqrt(3) x V x efficiency x PF), with V the line-to-line voltage. A 10 hp motor at 400 V, 90 percent efficiency and PF 0.85 draws 7460 / (1.732 x 400 x 0.9 x 0.85) = 14.08 A.

How many amps is a 5 hp motor?

It depends on the voltage, phases, efficiency and power factor. At 230 V single-phase with 90 percent efficiency and PF 0.85 the calculation gives 21.2 A. Use the nameplate for the actual value.

Is 1 hp equal to 746 watts?

The electrical horsepower used for motors is defined as exactly 746 W. The mechanical horsepower is about 745.7 W and the metric horsepower about 735.5 W. The difference is under 0.1 percent between the first two, so the calculator lets you pick.

Why do I need efficiency and power factor?

Horsepower is the mechanical output at the shaft, and the motor wastes some energy as heat. The input must be larger than the output by 1 / efficiency. For AC, the power factor tells how much of the supply current does useful work.

Why is the nameplate current different from the calculated current?

The nameplate figure is measured or specified for that particular motor at full load, using its real efficiency and power factor. A calculation with generic assumptions can differ by several percent, so the nameplate is the authoritative value.

Does this calculator size the breaker or the wire?

No. Breaker, fuse, cable and overload sizing follow local electrical codes and use specified tables and multipliers, not just the computed current. This tool gives an estimate of the full-load current to check a design against.

How do I convert kW to amps for a motor?

Select kW as the unit and enter the shaft power. The calculator uses the kW value directly as the output power, divides by efficiency for input power, and then applies the current formula for your supply.

What is the difference between hp to amps for single-phase and three-phase?

For the same power and voltage, a three-phase motor draws a lower line current because the formula has the square root of 3 in the denominator. The same 5 hp load is 21.2 A single-phase at 230 V but only 7.0 A per line on 400 V three-phase with the same efficiency and PF.

Does the current rise when the voltage drops?

Yes. For constant output power the current rises as the voltage falls, and a motor on a low supply can overheat. This is why voltage drop in long cable runs matters for motors.